Claude 24f816b6a3
Consolidate 22 sibling repos into layered organism structure
Place useful parts of the surrounding repos into sica-fondt by layer, per the
body model (Ada = membrane; brain/endocrine/capabilities/knowledge non-Ada):

- brain/        LLM reasoning + providers (dapr, hermes, MoMoA)
- capabilities/ REPRAG sidecars: hermes tools/skills, dapr tools, parallel
                dispatch, A51 channels, and the OSINT cluster
- knowledge/    LORAG corpus: 754 cyber-skills, agency personas, secure-coding,
                MITRE ATT&CK data
- reference/    defensive threat-reference (C3, shhbruh doc) + AdaYaml parser

License handling: AGPL sources (worldosint, advanced_evolution, mercury,
Reticulum) and GPL DeTTECT are SPEC-only clean-room/port descriptions — no
copyleft code copied. MIT/Apache/data parts copied as working trees.

Safety: shhbruh escape/persistence material and C3 covert-C2 kept as reference
only, not wired into the running organism. See CONSOLIDATION.md.

https://claude.ai/code/session_01UehUqEXXJJCsHoA4voCU5c
2026-06-10 06:53:01 +00:00

58 lines
1.7 KiB
Markdown

# ICS Anomaly Detection — API Reference
## Libraries
| Library | Install | Purpose |
|---------|---------|---------|
| pymodbus | `pip install pymodbus` | Modbus TCP/RTU client |
| requests | `pip install requests` | Historian and SIEM API access |
## Modbus TCP Protocol
| Function Code | Name | Risk |
|---------------|------|------|
| 1 | Read Coils | Low |
| 3 | Read Holding Registers | Low |
| 5 | Write Single Coil | Medium |
| 6 | Write Single Register | Medium |
| 15 | Write Multiple Coils | High |
| 16 | Write Multiple Registers | High |
| 43 | Read Device Identification | Recon |
## Common ICS Ports
| Port | Protocol | Description |
|------|----------|-------------|
| 502 | Modbus TCP | PLC communication |
| 102 | S7comm | Siemens S7 PLCs |
| 44818 | EtherNet/IP | Allen-Bradley / Rockwell |
| 20000 | DNP3 | Distributed Network Protocol |
| 4840 | OPC-UA | OPC Unified Architecture |
| 47808 | BACnet | Building automation |
## pymodbus Client Usage
```python
from pymodbus.client import ModbusTcpClient
client = ModbusTcpClient("192.168.1.10", port=502)
client.connect()
result = client.read_holding_registers(0, count=10, slave=1)
print(result.registers)
client.close()
```
## Anomaly Detection Thresholds
| Metric | Threshold | Severity |
|--------|-----------|----------|
| Unusual function codes | FC 8, 17, 43, 90+ | HIGH |
| Write frequency > 100/min | Burst writes | CRITICAL |
| Exception responses | Any exception code | MEDIUM |
| New source IP to PLC | Unauthorized access | CRITICAL |
## External References
- [pymodbus Docs](https://pymodbus.readthedocs.io/)
- [ICS-CERT Advisories](https://www.cisa.gov/ics-advisories)
- [NIST SP 800-82 Guide to ICS Security](https://csrc.nist.gov/publications/detail/sp/800-82/rev-3/final)