Claude 24f816b6a3
Consolidate 22 sibling repos into layered organism structure
Place useful parts of the surrounding repos into sica-fondt by layer, per the
body model (Ada = membrane; brain/endocrine/capabilities/knowledge non-Ada):

- brain/        LLM reasoning + providers (dapr, hermes, MoMoA)
- capabilities/ REPRAG sidecars: hermes tools/skills, dapr tools, parallel
                dispatch, A51 channels, and the OSINT cluster
- knowledge/    LORAG corpus: 754 cyber-skills, agency personas, secure-coding,
                MITRE ATT&CK data
- reference/    defensive threat-reference (C3, shhbruh doc) + AdaYaml parser

License handling: AGPL sources (worldosint, advanced_evolution, mercury,
Reticulum) and GPL DeTTECT are SPEC-only clean-room/port descriptions — no
copyleft code copied. MIT/Apache/data parts copied as working trees.

Safety: shhbruh escape/persistence material and C3 covert-C2 kept as reference
only, not wired into the running organism. See CONSOLIDATION.md.

https://claude.ai/code/session_01UehUqEXXJJCsHoA4voCU5c
2026-06-10 06:53:01 +00:00

1.6 KiB

API Reference: Detecting Modbus Protocol Anomalies

Modbus Protocol Limits

Parameter Maximum Value
Coil read quantity 2000
Register read quantity 125
Register write quantity 123
Unit ID range 1-247
PDU size 253 bytes

Anomaly Detection Methods

Anomaly Detection Severity
Timing deviation Polling interval outside tolerance MEDIUM-HIGH
Excessive read Quantity > protocol limits HIGH
Invalid function code Not in standard set HIGH
Modbus scan >5 unique function codes from source HIGH
Register range violation Address outside configured range MEDIUM

Zeek Modbus Log Fields

#fields ts uid id.orig_h id.orig_p id.resp_h id.resp_p func exception quantity

Suricata Modbus Rules

alert modbus any any -> any 502 (msg:"Modbus Invalid Function Code"; \
  modbus: function !1,!2,!3,!4,!5,!6,!15,!16; sid:4000001;)
alert modbus any any -> any 502 (msg:"Modbus Excessive Register Read"; \
  modbus: function 3; modbus: quantity > 125; sid:4000002;)

Scapy Modbus Analysis

from scapy.contrib.modbus import ModbusADURequest
from scapy.all import rdpcap

pkts = rdpcap("modbus.pcap")
for pkt in pkts:
    if pkt.haslayer(ModbusADURequest):
        print(f"FC={pkt.funcCode} Len={pkt.len}")

Baseline Monitoring

# Expected polling behavior
expected_interval = 1.0  # seconds
tolerance = 0.5
# Alert if interval < 0.5s or > 3.0s

CLI Usage

python agent.py --modbus-log modbus.log
python agent.py --modbus-log modbus.log --expected-interval 2.0